Image

IMAGE
:


4kW~12kW/220V~240V Off-grid PV Kits

Fortune Energy provides turnkey solutions of off grid PV system for customers. Off-grid/island system usually includes photovoltaic module, battery pack, off-grid inverter and racking. Fortune Energy will customize a modular, scalable and optional off-grid integrated system according to the site conditions and the power demand of customers.
BRAND
:
MODEL
:
FESS-F
POWER
:
4kW~12kW/220VAC~240VAC
MODULE
:
Poly or Mono
SYSTEM TYPE
:
Off-grid Split-style
INVERTER
:
4kW~12kW Off-grid Single-Phase
BATTERY
:
Li-on/Lead-acid
WARRANTY
:
System 1 Year; Modules 25 Years; Inverter 1 Year
  • DETAILS
MODELFESS-F4KFESS-F5KFESS-F6KFESS-F8KFESS-F10KFESS-F12K
Nominal Battery System Voltage24V48V24V48V48V48VDC48VDC48VDC
INVERTER OUTPUT
Rated power4KW5KW6KW8.0KW10.0KW12.0KW
Surge rating(20ms)12KW15KW18KW24KW30KW36KW
Capable of starting electric motor2HP2HP3HP4HP5HP6HP
WaveformPure sine wave / same as input (bypass mode)
Nominal output voltage RMS220V / 230V / 240VAC (+/-10%RMS)
Output frequency50Hz / 60Hz +/- 0.3Hz
Inverter effciency(peak)>85%>88%
Line mode efficiency>95%
Power factor1.0
Typical transfer time20ms(max)
AC INPUT
Voltage230VAC
Selectable voltage range90-280 VAC (APL)
Frequency range50Hz / 60Hz
BATTERY
Low battery voltage cutoff20-24VDC for 24VDC mode (40-48VDC for 48VDC mode)
Low battery voltage recover21-25VDC for 24VDC mode (42-50VDC for 48VDC mode)
High battery voltage cutoff30VDC for 24VDC mode (60VDC for 48VDC mode)
High battery voltage recover28.5VDC for 24VDC mode (57VDC for 48VDC mode)
Idle consumption-search mode<30W when power saver on<60W when power saver on
AC CHARGER
Output voltageDepends on battery type
Charger AC input breaker rating40A40A50A80A80A80A
Overcharge protection S.D.31.4VDC for 24VDC mode (62.8VDC for 48VDC mode )
Maximum charge current80A60A100A70A80A100A120A140A
BTS
Continuous output powerYes Variances in charging voltage & S.D. voltage base on the battery temperature
BYPASS PROTECTION
Input voltage waveformSine wave (grid or generator)
Nominal input frequency50Hz or 60Hz
Overload protection (SMPS Load)Circuit breaker
Output short circuit protectionCircuit breaker
Bypass breaker rating40A63A63A63A
Max bypass current40Amp80Amp
SOLAR CHARGER
Maximum PV charge current80A100A(200A optional)
DC voltage24V/48V Auto work48V
Maximim PV array power2000W4000W2000W4000W4000W5000W(10000W for 200A optional)
MPPT range @ operating voltage(VDC)32-145VDC for 24V mode,64-147V for 48V mode64~147VDC
Maximum PV array open circuit voltage147VDC
Maximum effciency>98%
Standby power consumption<2W
OTHER
Operation temperature range0°C to 40°C
Storage temperature-15°C to 60°C
Audible noise60dB MAX
DisplayLED+LCD
©2024  FORTUNE ENERGY TECHNOLOGY CO., LTD.   All Rights Reserved.
info@fortunenergy.com

Search